Automatic operation correct
Y
Manual operation correct
Y
Current reading - Red
11
Current reading - White
10.5
Current reading - Blue
10.6
Run hour reading
756187
Any interlocks operational
Y
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Na- Insulation resistance, U-E 290 M ohm, V-E 297M ohm, W-E 295M ohm

Motor Tag