SPS201
Automatic operation correct
Y
Manual operation correct
Y
Current reading - Red
5.9
Current reading - White
5.8
Current reading - Blue
6
Run hour reading
Na
Any interlocks operational
Y
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Pull fuse yes
Motor Tag
- Site-Motor-Pump 2
SPS201
Automatic operation correct
Y
Manual operation correct
Y
Current reading - Red
6.9
Current reading - White
6.8
Current reading - Blue
6.8
Run hour reading
Na,
Any interlocks operational
Y
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Pull fuse yes
Motor Tag
- Site-Motor-Pump 1
Sps121
Automatic operation correct
Y
Manual operation correct
Y
Current reading - Red
8.0
Current reading - White
7.9
Current reading - Blue
7.8
Run hour reading
341480
Any interlocks operational
Y
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Pull fuse yes , 1.7, 2.0, 1.9 ohms
Motor Tag
- Site-Motor-Pump 2
Sps121
Automatic operation correct
Y
Manual operation correct
Y
Current reading - Red
8.9
Current reading - White
8.6
Current reading - Blue
8.7
Run hour reading
543640
Any interlocks operational
Y
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Pull fuse yes. 1.7, 1.9, 1.9 ohms
Motor Tag
- Site-Motor-Pump 1
Sps215
Automatic operation correct
Y
Manual operation correct
Y
Current reading - Red
23
Current reading - White
24
Current reading - Blue
23
Run hour reading
Na 5.0, 5.5, 4.9 ohms between windings
Any interlocks operational
Y
PLC input/output operational
Y
SCADA feedback operational
H
Perform a manual trip to test fault conditions
Pull fuse yes
Motor Tag
- Site-Motor-Pump 2
Sps215
Automatic operation correct
Y
Manual operation correct
Y
Current reading - Red
23
Current reading - White
23
Current reading - Blue
25
Run hour reading
Na
Any interlocks operational
Y
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Pull fuse yes
Motor Tag
- Site-Motor-Pump 1