The installation has an earthing system that is correctly rated (where applicable)
Yes
Relies on manufacturers instructions
Yes
Specify type of supply system
MEN 230v
Part 2 AS/NZS 3000
Yes
Contact Name
Lamberts
Contact Address
46 Water Street
Name(s) of Persons Supervised
Dontay Fusitua-Joass
Email
Brian.Firth@mckay.co.nz
Polarity
Correct
Insulation resistance
680 M-ohm
Earth Continuity
0.35 ohm
Bonding
n/a
Fault Loop impedance
0.56 ohm
Other (specify)
PSCC = 0.4 kA
Connection Date
Certificate Issue Date
Addition
No
Low Risk
Yes
Contains fittings that are safe to connect to a power supply
Yes
General
No
New Work
No
High Risk
No
Replaced faulty 15 amp GPO with a commercial grade 15 amp GPO.
DB1-B4.
RCD test results: x1@0Deg = 28mS. x1@180Deg = 18mS. Ramp = 22mA.
Alteration
On
Part 1 of AS/NZS 3000
Off
Parts of the installation to which this certificate relates that are safe to connect to a power supply
All
Specify Parts
15 amp socket-outlet for water blaster
Manufacturers Instructions
https://www.jarussell.co.nz/Compliance
The work has been done in accordance with a certified design
No
The work relies on a Supplier Declaration of Conformity (SDoC)
Yes
Supplier Declaration of Conformitytxt
https://www.jarussell.co.nz/Compliance
The installation has been satisfactorily tested in accordance with the Electricity (Safety) Regulations 2010
Yes