Technician
- Brian.Firth
Inspection Date
Location
Reeves Street, Ruawai, Dargaville
Phone
027 355 2248
CompanyDivision
Northland Maintenance
The installation has an earthing system that is correctly rated (where applicable)
Yes
Relies on manufacturers instructions
Yes
Specify type of supply system
MEN 230v
Part 2 AS/NZS 3000
Yes
Contact Name
Michael Fowlie
Contact Address
Downer - Dargaville
Email
Brian.Firth@mckay.co.nz
Polarity
Correct
Insulation resistance
> 999 M-
Earth Continuity
0.13
Bonding
n/a
Fault Loop impedance
0.74
PSCC
0.31
Connection Date
Certificate Issue Date
Addition
Yes
Low Risk
No
Contains fittings that are safe to connect to a power supply
Yes
General
Yes
New Work
No
High Risk
No
New 2.5mm cct from R7 on C20 MCB.
New DB in chlorine shed.
New light on 1.5mm on C6 MCB.
New GPO on 2.5mm on C16 RCBO (RCD test results = 22mS and 23mA).
New pump outlets on 2.5mm on C10 MCB.
Alteration
Off
Part 1 of AS/NZS 3000
Off
Parts of the installation to which this certificate relates that are safe to connect to a power supply
All
Specify Parts
Chlorine shed DB and FSC
Manufacturers Instructions
https://www.jarussell.co.nz/Compliance
The work has been done in accordance with a certified design
No
The work relies on a Supplier Declaration of Conformity (SDoC)
Yes
Supplier Declaration of Conformitytxt
https://www.jarussell.co.nz/Compliance
The installation has been satisfactorily tested in accordance with the Electricity (Safety) Regulations 2010
Yes