Site Name

  • siteinfo-WTP 201 lower

Technician

  • ChaiMahabal
Inspection Date
Check the battery condition
Needs Replacement
Check power supply voltage, record voltage
Good
Load test system with electronic load for 5 secs, record voltable (limit 11.5V)
Done
Test Charger and record result
NA
Load test battery with electronic load for 1 min, record voltage (limit 11.5V)
Done
Reconnect battery and monitor battery voltage rise
Done
Battery installation date
Check aerial, pole and coax cable for damage
Good
Enclosure free of rust/corrosion
Generator Box needs lock fixed
Equipment not damaged
Yes
Free from any insect or vermin infestation
Yes
Attach laptop and check unit communicates with I/O
Y
Test each input to the telemetry system by starting and stopping equipment
Y
Activate accessible inputs and test instruments or relay inputs at telemetry terminals
Y
All site outputs are transmitted to the laptop computer
Y
Test site alarm output is transmitted
Y
Recommendations
  1. Add 3x led lights 60W phillips on 3 sides of the chemical dosing building. 
  2. Remove 2 x end boxes in the room behind the poly dosing above level. 
  3. Replace 1 x 12-45ah battery. - Please Create a battery register for future battery changes if possible.
  4. Test and tag - Good till 21/01/2027 ( Please Schedule this for the next year if this is possible on software).
  5. Rcd tested - 1x 37.0ms 2x17.1ms 5x7.6ms Test button OK
  6. Replace lock mechanism for the generator supply box .
  7. The in wall exhaust fan is the vsd chamber does not work - Also there is opening to get to it (May be installed with vsds and no provision made for a future replacement) It high temperature in there. Also needs large vents at the bottom.
  8. There is another in wall exhaust fan has got no supply to it for the ventilation. Does this need to be connected as well ? 
  9. Generator Page to be updated for WTP Bottom - Only Leads 125A and Top Plant - 125A Socket.

     

Overall Checked
No