Site Name
- siteinfo-WTP 201 lower
Technician
- ChaiMahabal
Inspection Date
Check the battery condition
Needs Replacement
Check power supply voltage, record voltage
Good
Load test system with electronic load for 5 secs, record voltable (limit 11.5V)
Done
Test Charger and record result
NA
Load test battery with electronic load for 1 min, record voltage (limit 11.5V)
Done
Reconnect battery and monitor battery voltage rise
Done
Battery installation date
Check aerial, pole and coax cable for damage
Good
Enclosure free of rust/corrosion
Generator Box needs lock fixed
Equipment not damaged
Yes
Free from any insect or vermin infestation
Yes
Attach laptop and check unit communicates with I/O
Y
Test each input to the telemetry system by starting and stopping equipment
Y
Activate accessible inputs and test instruments or relay inputs at telemetry terminals
Y
All site outputs are transmitted to the laptop computer
Y
Test site alarm output is transmitted
Y
Recommendations
- Add 3x led lights 60W phillips on 3 sides of the chemical dosing building.
- Remove 2 x end boxes in the room behind the poly dosing above level.
- Replace 1 x 12-45ah battery. - Please Create a battery register for future battery changes if possible.
- Test and tag - Good till 21/01/2027 ( Please Schedule this for the next year if this is possible on software).
- Rcd tested - 1x 37.0ms 2x17.1ms 5x7.6ms Test button OK
- Replace lock mechanism for the generator supply box .
- The in wall exhaust fan is the vsd chamber does not work - Also there is opening to get to it (May be installed with vsds and no provision made for a future replacement) It high temperature in there. Also needs large vents at the bottom.
- There is another in wall exhaust fan has got no supply to it for the ventilation. Does this need to be connected as well ?
-
Generator Page to be updated for WTP Bottom - Only Leads 125A and Top Plant - 125A Socket.
Overall Checked
No