Dargaville WWTP Inlet Screen
Phone
027 355 2248
CompanyDivision
Northland Maintenance
The installation has an earthing system that is correctly rated (where applicable)
Yes
Relies on manufacturers instructions
No
Specify type of supply system
MEN system - 230v
Part 2 AS/NZS 3000
Yes
Contact Name
United Civil
Email
Brian.firth@mckay.co.nz
Polarity
Correct
Insulation resistance
> 999
Earth Continuity
0.5
Bonding
0.02
Fault Loop impedance
1.01
PSCC
0.23
Connection Date
Certificate Issue Date
Addition
Yes
Low Risk
No
Contains fittings that are safe to connect to a power supply
Yes
General
Yes
New Work
No
High Risk
No

Add 3-phase circuit to MEN switchboard:

C20 MCB. 110m of 6mm 4c+E circ TPS. Via underground duct, then trunking and tray into outdoor controls cabinet (by others).

EFLI at the MEN switchboard is 0.14 ohms with PSCC 1.7 kA.

EFLI at the control cabinet is 1.01 ohms with PSCC 0.23 kA.

Alteration
Off
Part 1 of AS/NZS 3000
Off
Parts of the installation to which this certificate relates that are safe to connect to a power supply
All
Specify Parts
Supply to inlet screen control cabinet
The work has been done in accordance with a certified design
No
The work relies on a Supplier Declaration of Conformity (SDoC)
No
The installation has been satisfactorily tested in accordance with the Electricity (Safety) Regulations 2010
Yes
Repair