Technician
- Brian.Firth
Inspection Date
Location
Foodstuffs 26 Te Waiiti Place, Raumanga, Whangārei
Phone
027 355 2248
CompanyDivision
Northland Maintenance
The installation has an earthing system that is correctly rated (where applicable)
Yes
Relies on manufacturers instructions
Yes
Specify type of supply system
MEN system - 230v
Part 2 AS/NZS 3000
Yes
Contact Name
Dennis Khan
Contact Address
26 Te Waiiti Place
Email
Brian.firth@mckay.co.nz
Polarity
Correct
Insulation resistance
N/A
Earth Continuity
0.4
Bonding
N/A
Fault Loop impedance
0.79
PSCC
0.29
Connection Date
Certificate Issue Date
Addition
No
Low Risk
No
Contains fittings that are safe to connect to a power supply
Yes
General
Yes
New Work
No
High Risk
No
Replaced the existing 56CV310 socket-outlet, with a 56CV315. This is on a dedicated circuit from DB1-R19 using 10mm 2c+E circ TPS on C20 MCB. Approx 70m run.
Alteration
On
Part 1 of AS/NZS 3000
Off
Parts of the installation to which this certificate relates that are safe to connect to a power supply
All
Specify Parts
External socket-outlet for truck-wash water-blaster
Manufacturers Instructions
https://www.jarussell.co.nz/Compliance
The work has been done in accordance with a certified design
No
The work relies on a Supplier Declaration of Conformity (SDoC)
Yes
Supplier Declaration of Conformitytxt
https://www.jarussell.co.nz/Compliance
The installation has been satisfactorily tested in accordance with the Electricity (Safety) Regulations 2010
Yes
Repair
Off