MicroWave Oven

Appliance Details
Media- 315220/EM720C-PM0F00
Test Instrument
UNIT-T
Insulation Resistance
>250 M Ohm
Correct Circuit Connections
Yes
Continuity
0.1 Ohm
Test Tag ID Number
310001
Expiry Date
Result
Pass

Refrigerator

Appliance Details
HAIER- HBF165W S/N - BS06H1E7X00BKC8H0038
Test Instrument
UNI-T
Insulation Resistance
>250 M Ohm
Correct Circuit Connections
Yes
Continuity
0.34 Ohm
Test Tag ID Number
310000
Expiry Date
Result
Pass

Test and tag WTP301 Appliances

Inspection Date

Site Name

  • siteinfo-WTP 301

Technician

  • Kushan.Appuhamilage
Job Number
2526-A1.2

Tag and Test Lineitem

  • MicroWave Oven
  • Refrigerator
  • Kettle
  • Verifone PSU Cable
  • Verifone PSU
  • IEC C13 Power Cable Monitor
  • IEC C13 Power chord- NOZMOI router PSU
  • IEC C13 Power Chord CPU
Overall Checked
No

P2 submersable pump

Automatic operation correct
y
Manual operation correct
y
Current reading - Red
3.1A
Current reading - White
3.1A
Current reading - Blue
3.2A
Run hour reading
N.A.
Any interlocks operational
phase fail relay
PLC input/output operational
y
SCADA feedback operational
y
Perform a manual trip to test fault conditions
y

Motor Tag

  • Site-Motor-Pump 2

P1 submersable pump

Automatic operation correct
y
Manual operation correct
y
Current reading - Red
3A
Current reading - White
3A
Current reading - Blue
3A
Run hour reading
N.A
Any interlocks operational
Phase fail relay
PLC input/output operational
y
SCADA feedback operational
y
Perform a manual trip to test fault conditions
y

Motor Tag

  • Site-Motor-Pump 1

submersable pump1

Automatic operation correct
Power factor capacitors
Manual operation correct
Y
Current reading - Red
1.8A
Current reading - White
2.2A
Current reading - Blue
1.9A
Run hour reading
N.A.
Any interlocks operational
Y overload protected and phase failure relay operational
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Y

Motor Tag

  • Site-Motor-Pump 1

DOL

Automatic operation correct
Y
Manual operation correct
Y
Current reading - Red
2.69A
Current reading - White
2.89A
Current reading - Blue
2.92A
Run hour reading
N.A.
Any interlocks operational
Y minicas
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Y

Motor Tag

  • Site-Motor-Pump 2

Pump 1

Automatic operation correct
Correct
Manual operation correct
Correct
Current reading - Red
6.2A
Current reading - White
6.3A
Current reading - Blue
6.3A
Run hour reading
N/A
Any interlocks operational
Yes on auto mode
PLC input/output operational
Yes
SCADA feedback operational
Yes
Perform a manual trip to test fault conditions
Yes

Motor Tag

  • Site-Motor-Pump 1

Flygt submersable pump

Automatic operation correct
Y
Manual operation correct
Y
Current reading - Red
40.2A
Current reading - White
40.2A
Current reading - Blue
40.2A
Run hour reading
N.A.
Any interlocks operational
N.A.
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Y

Motor Tag

  • Site-Motor-Pump 2
Subscribe to