SPS222 PUMP2

Automatic operation correct
Y
Manual operation correct
Y
Current reading - Red
3.6
Current reading - White
3.7
Current reading - Blue
3.7
Run hour reading
Na
Any interlocks operational
Y
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Y

Motor Tag

  • Site-Motor-PUMP 2

SPS222 PUMP1

Automatic operation correct
Y
Manual operation correct
Y
Current reading - Red
3.7
Current reading - White
3.6
Current reading - Blue
3.7
Run hour reading
Na
Any interlocks operational
Y
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Y

Motor Tag

  • Site-Motor-PUMP 1

SPS220 Pump2

Automatic operation correct
Y
Manual operation correct
Y
Current reading - Red
28.3
Current reading - White
28.4
Current reading - Blue
28.1
Run hour reading
Na
Any interlocks operational
Y
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Na

Motor Tag

  • Site-Motor-PUMP 2

SPS220 Pump1

Automatic operation correct
Y
Manual operation correct
Y
Current reading - Red
22.1
Current reading - White
22.4
Current reading - Blue
22.3
Run hour reading
Na
Any interlocks operational
Y
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Na

Motor Tag

  • Site-Motor-PUMP 1

SPS221 PUMP2

Automatic operation correct
Y
Manual operation correct
Y
Current reading - Red
5.2
Current reading - White
5.1
Current reading - Blue
5.2
Run hour reading
Na
Any interlocks operational
Y
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Y

Motor Tag

  • Site-Motor-PUMP 2

SPS221 PUMP1

Automatic operation correct
Y
Manual operation correct
Y
Current reading - Red
5.1
Current reading - White
5.0
Current reading - Blue
5.0
Run hour reading
Na
Any interlocks operational
Y
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Y

Motor Tag

  • Site-Motor-PUMP 1

SPS216 PUMP2

Automatic operation correct
Y
Manual operation correct
Y
Current reading - Red
3.2
Current reading - White
3.3
Current reading - Blue
3.3
Run hour reading
Na
Any interlocks operational
Y
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Na

Motor Tag

  • Site-Motor-PUMP 2

SPS216 Pump1

Automatic operation correct
Y
Manual operation correct
Y
Current reading - Red
3.1
Current reading - White
3.2
Current reading - Blue
3.2
Run hour reading
Na
Any interlocks operational
Y
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Na

Motor Tag

  • Site-Motor-PUMP 1

SPS215 Ngaere st pump2

Automatic operation correct
Y
Manual operation correct
Y
Current reading - Red
7.9
Current reading - White
8.1
Current reading - Blue
8.1
Run hour reading
Na
Any interlocks operational
Y
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Na

Motor Tag

  • Site-Motor-Pump 2