SPS202

Automatic operation correct
Y
Manual operation correct
Y
Current reading - Red
6.9
Current reading - White
6.8
Current reading - Blue
6.8
Run hour reading
Na 2.7,2.8,2.9 ohms between windings
Any interlocks operational
Yes
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Pull fuse yes

Motor Tag

  • Site-Motor-Pump 2

SPS202

Automatic operation correct
Y
Manual operation correct
Y
Current reading - Red
7.0
Current reading - White
7.1
Current reading - Blue
7.0
Run hour reading
Na 2.9,3.0,3.0 ohms between windings
Any interlocks operational
Yes
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Pull fuse yes

Motor Tag

  • Site-Motor-Pump 1

Sps214

Automatic operation correct
Y
Manual operation correct
Y
Run hour reading
Na
Any interlocks operational
Y
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Pull fuse yes

Motor Tag

  • Site-Motor-Pump 2

Sps214

Automatic operation correct
Y
Manual operation correct
Y
Run hour reading
Na
Any interlocks operational
Y
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Pull fuse yes

Motor Tag

  • Site-Motor-Pump 1

Sps111

Automatic operation correct
Y
Manual operation correct
Y
Current reading - Red
4.9
Current reading - White
5.0
Current reading - Blue
5.1
Run hour reading
Na
Any interlocks operational
Y
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Y

Motor Tag

  • Site-Motor-Pump 2

Sps111

Automatic operation correct
Y
Manual operation correct
Y
Current reading - Red
5.7
Current reading - White
5.6
Current reading - Blue
5.7
Run hour reading
Na
Any interlocks operational
Y
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Y pull fuse

Motor Tag

  • Site-Motor-Pump 1

Sps110

Automatic operation correct
Y
Manual operation correct
Y
Current reading - Red
5.6
Current reading - White
5.6
Current reading - Blue
5.5
Run hour reading
Na thermal 47.9
Any interlocks operational
Y
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Pull fuse yes

Motor Tag

  • Site-Motor-Pump 2

Sps110

Automatic operation correct
Y
Manual operation correct
Y
Current reading - Red
6.4
Current reading - White
6.2
Current reading - Blue
6.0
Run hour reading
Na thermal 52.1 ohms
Any interlocks operational
Y
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Pull fuse yes

Motor Tag

  • Site-Motor-Pump 1