P2 submersable pump
Automatic operation correct
y
Manual operation correct
y
Current reading - Red
3.1A
Current reading - White
3.1A
Current reading - Blue
3.2A
Run hour reading
N.A.
Any interlocks operational
phase fail relay
PLC input/output operational
y
SCADA feedback operational
y
Perform a manual trip to test fault conditions
y
Motor Tag
- Site-Motor-Pump 2
P1 submersable pump
Automatic operation correct
y
Manual operation correct
y
Current reading - Red
3A
Current reading - White
3A
Current reading - Blue
3A
Run hour reading
N.A
Any interlocks operational
Phase fail relay
PLC input/output operational
y
SCADA feedback operational
y
Perform a manual trip to test fault conditions
y
Motor Tag
- Site-Motor-Pump 1
submersable pump1
Automatic operation correct
Power factor capacitors
Manual operation correct
Y
Current reading - Red
1.8A
Current reading - White
2.2A
Current reading - Blue
1.9A
Run hour reading
N.A.
Any interlocks operational
Y overload protected and phase failure relay operational
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Y
Motor Tag
- Site-Motor-Pump 1
DOL
Automatic operation correct
Y
Manual operation correct
Y
Current reading - Red
2.69A
Current reading - White
2.89A
Current reading - Blue
2.92A
Run hour reading
N.A.
Any interlocks operational
Y minicas
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Y
Motor Tag
- Site-Motor-Pump 2
Pump 1
Automatic operation correct
Correct
Manual operation correct
Correct
Current reading - Red
6.2A
Current reading - White
6.3A
Current reading - Blue
6.3A
Run hour reading
N/A
Any interlocks operational
Yes on auto mode
PLC input/output operational
Yes
SCADA feedback operational
Yes
Perform a manual trip to test fault conditions
Yes
Motor Tag
- Site-Motor-Pump 1
Flygt submersable pump
Automatic operation correct
Y
Manual operation correct
Y
Current reading - Red
40.2A
Current reading - White
40.2A
Current reading - Blue
40.2A
Run hour reading
N.A.
Any interlocks operational
N.A.
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Y
Motor Tag
- Site-Motor-Pump 2