SPS314 pump 2

Automatic operation correct
Y
Manual operation correct
Y
Current reading - Red
3.7
Current reading - White
3.6
Current reading - Blue
3.7
Run hour reading
Na
Any interlocks operational
Y
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Y

Motor Tag

  • Site-Motor

SPs314 pump 1

Automatic operation correct
Y
Manual operation correct
Y
Current reading - Red
4.0
Current reading - White
3.9
Current reading - Blue
3.9
Run hour reading
Na
Any interlocks operational
Y
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Y

Motor Tag

  • Site-Motor-Pump 1

SPS311 pump 2

Automatic operation correct
Y
Manual operation correct
Y
Current reading - Red
10.3
Current reading - White
10.6
Current reading - Blue
9.9
Run hour reading
8844
Any interlocks operational
Y
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Na- insulation resistance U-E 999 ohm, V-E 999 MOHM, W-E 999 M OHM -

Motor Tag

  • Site-Motor-Pump 2

SPs311 pump 1

Automatic operation correct
Y
Manual operation correct
Y
Current reading - Red
11
Current reading - White
10.5
Current reading - Blue
10.6
Run hour reading
756187
Any interlocks operational
Y
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Na- Insulation resistance, U-E 290 M ohm, V-E 297M ohm, W-E 295M ohm

Motor Tag

  • Site-Motor-Pump 1

Auto Drain

Comment
New Lead made for the auto drain
Appliance Details
Compressor auto drain plug
Test Instrument
Metrel Pat
Insulation Resistance
L-N->200M , N-E->200M , L-E->200M
Correct Circuit Connections
Yes
Continuity
0.1
Test Tag ID Number
311470
Expiry Date
Result
Pass

Auto Drain - compressor

Comment
Brand New Lead Made and Tested
Appliance Details
Lead for auto drain
Test Instrument
Metrel Pat
Insulation Resistance
L-N->200M , N-E->200M , L-E->200M
Correct Circuit Connections
Yes
Continuity
0.1
Test Tag ID Number
311471
Expiry Date
Result
Pass

WTP501

Inspection Date

Site Name

  • siteinfo-WTP 501

Technician

  • ChaiMahabal
Job Number
0226-K

Tag and Test Lineitem

  • Auto Drain - compressor
  • Auto Drain
Overall Checked
No

Sps905 2

Automatic operation correct
Y
Manual operation correct
Y
Current reading - Red
7.8
Current reading - White
7.7
Current reading - Blue
7.7
Run hour reading
0115879
Any interlocks operational
Y
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Na

Motor Tag

  • Site-Motor-Pump 2

Sps905 1

Automatic operation correct
Y
Manual operation correct
Y
Current reading - Red
12.4
Current reading - White
12.5
Current reading - Blue
12.7
Run hour reading
0149120
Any interlocks operational
Y
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Na

Motor Tag

  • Site-Motor-Pump 1

Sps904 2

Automatic operation correct
Y
Manual operation correct
Y
Current reading - Red
6.8
Current reading - White
6.8
Current reading - Blue
6.9
Run hour reading
0112125
Any interlocks operational
Y
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Between windings 1.8 ohms

Motor Tag

  • Site-Motor-Pump 2