Sps214
Automatic operation correct
Y
Manual operation correct
Y
Run hour reading
Na
Any interlocks operational
Y
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Pull fuse yes
Motor Tag
- Site-Motor-Pump 2
Sps214
Automatic operation correct
Y
Manual operation correct
Y
Run hour reading
Na
Any interlocks operational
Y
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Pull fuse yes
Motor Tag
- Site-Motor-Pump 1
Sps111
Automatic operation correct
Y
Manual operation correct
Y
Current reading - Red
4.9
Current reading - White
5.0
Current reading - Blue
5.1
Run hour reading
Na
Any interlocks operational
Y
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Y
Motor Tag
- Site-Motor-Pump 2
Sps111
Automatic operation correct
Y
Manual operation correct
Y
Current reading - Red
5.7
Current reading - White
5.6
Current reading - Blue
5.7
Run hour reading
Na
Any interlocks operational
Y
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Y pull fuse
Motor Tag
- Site-Motor-Pump 1
Sps110
Automatic operation correct
Y
Manual operation correct
Y
Current reading - Red
5.6
Current reading - White
5.6
Current reading - Blue
5.5
Run hour reading
Na thermal 47.9
Any interlocks operational
Y
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Pull fuse yes
Motor Tag
- Site-Motor-Pump 2
Sps110
Automatic operation correct
Y
Manual operation correct
Y
Current reading - Red
6.4
Current reading - White
6.2
Current reading - Blue
6.0
Run hour reading
Na thermal 52.1 ohms
Any interlocks operational
Y
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Pull fuse yes
Motor Tag
- Site-Motor-Pump 1
Sps109
Automatic operation correct
Y
Manual operation correct
Y
Current reading - Red
6.1
Current reading - White
6.2
Current reading - Blue
6.0
Run hour reading
Na
Any interlocks operational
Y
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Y pull fuse
Motor Tag
- Site-Motor-Pump 2
SPS109
Automatic operation correct
Y
Manual operation correct
Y
Current reading - Red
5.4
Current reading - White
5.3
Current reading - Blue
5.5
Run hour reading
Na 3.4, 3.4, 3.4 ohms across all windings
Any interlocks operational
Y
PLC input/output operational
Y
SCADA feedback operational
Y
Perform a manual trip to test fault conditions
Y pull fuse
Motor Tag
- Site-Motor-Pump 1